What fill valve run time says about water level control, Waterline Controls
Written by Waterline Controls

What Fill Valve Run Time Says About Water Level Control

Fill valve run time is the total time a water level controller calls for makeup water over a defined period. A BMS can trend that fill command from the controller’s fill dry contact. It shows when makeup demand changes, but it does not measure gallons, and valve feedback or a flow meter is needed to confirm that water was actually delivered.

Start by Establishing a Baseline

A cooling tower or tank has a baseline filling pattern for a given operating load. That pattern depends on load, evaporation, blowdown, weather, production demand and other factors.

Waterline Controls notes on its WS4500 water level controller page that the fill dry contacts can be used comparatively to develop a baseline benchmark of water usage for the system. A BMS can log each fill start and stop as a change in that contact. The alarm and power loss contacts available depend on the model.

Trend that point long enough to understand what normal looks like before deciding that a change indicates a fault.

Watch for Longer Fill Cycles

If the fill command stays active much longer than usual, several possibilities deserve investigation.

The system may genuinely be using more water. The fill valve or strainer may also be restricting flow, causing the basin to recover more slowly. In a cooling tower, hotter weather or increased building load can naturally increase makeup requirements.

The WLC-6100T controller also flags a prolonged fill command locally: its status light shows steady red for one minute after six hours of continuous fill command.

The trend therefore provides a clue, not a diagnosis. Compare fill run time with operating conditions before dispatching maintenance.

Watch for More Frequent Filling

More frequent fill cycles can indicate a different problem. Water may be escaping from the system, the operating band may have changed or the controller may be responding to unusual level movement.

A leaking drain or excessive blowdown can increase fill calls. If the level rises between calls instead, check whether the fill valve passes water after its closing time. See why slow closing fill valves matter for water level control.

Waterline Controls’ guidance on water level controls for building automation notes that some chemical treatment companies use a “bleed and feed” method that drains water as they add chemical, which costs water and, in some cases, causes unnecessary chemical use.

Use a Meter When Gallons Matter

Fill run time should not be presented as direct water consumption unless the system also has reliable flow information. Fill command run time gives duration. A makeup water meter, or a flow meter with totalization, gives volume.

If water conservation reporting requires actual gallons, use the appropriate metering equipment and trend both values where useful. The level controller status then shows when the controller called for makeup and helps investigate changes in measured use.

Add Context to BMS Trends

Trend fill status alongside other points that help explain changes in fill demand.

For a cooling tower, that might include fan operation, condenser water temperature, recirculating water conductivity and blowdown status. For a storage tank, it might include pump status, low alarm and high alarm.

The objective is not to collect every possible point. It is to give the facility enough information to identify a change from normal behavior. For a full point list, see what BMS points a water level controller should report.

Investigate Before Adjusting Setpoints

A common response to frequent filling is to change the control levels. That may hide the symptom without correcting the cause.

Inspect the valve, water supply, basin, piping and actual operating conditions first. If the original control band remains appropriate, leave it alone.

Water Level Controllers With Fill Status Outputs

Waterline Controls manufactures frequency-based electronic level controllers with dry contacts for BMS and BAS integration. The WLC-5000 water level controller, for example, provides a fill command contact that can be trended to establish a comparative operating baseline, alongside high alarm, low alarm and power loss contacts. Call 480-905-1892 to discuss the points available on your controller and how fill monitoring fits into the facility’s water management plan.

References

WS4500 water level controller with fill and low alarm

Water level controls for building automation

WLC-5000 water level controller with high and low alarms

WLC-6100T controller installation instructions