Water level control commissioning checklist: sensor points, alarms, BMS signals and power loss
Written by Waterline Controls

Water Level Control Commissioning Checklist

Water level control commissioning is the process that verifies and documents that the installed sensors, controller outputs, connected equipment and remote points respond as specified in the approved sequence of operation. A water level controller can be wired correctly and still fail to deliver the intended sequence.

Sensor elevations may be wrong. A fill valve may be connected to the wrong relay. The BMS may interpret an alarm contact in reverse. A pump may start correctly but stop at the wrong point. Commissioning should prove the complete system, not just confirm that the panel powers up.

Review the Sequence Before Testing

Begin with the approved drawings and sequence of operation.

Identify every intended function, including fill start, fill stop, pump start, pump stop, high alarm, low alarm and any second pump or heater function. Compare those points with the actual sensor elevations, using the principles in our water level sensor placement guide for level controls. For heater functions, see basin heater low water protection for cooling tower level controls.

Waterline Controls offers custom sensor lengths and extension kits for compatible probes, so record the installed dimensions rather than assuming them from a standard drawing.

Verify the Panel Before Operating Equipment

Confirm the correct supply voltage, grounding and wiring before testing outputs. For Waterline Controls installations, verify that the sensor cable runs in earth-grounded metal conduit separate from high voltage conduit, as the installation instructions specify. Check that the panel indicators match the actual tank condition.

If the controller reports to a BMS or SCADA system, confirm that the remote system shows the controller in its normal state before functional testing begins.

Identify which loads may operate during testing and which must be isolated under the approved test procedure.

Test Each Water Level Function

Verify the installed elevations and observe the actual trip points as the water rises and falls under the approved test procedure. Use approved simulations to check logic and remote signals, and record which actual water responses still need to be verified.

For a fill system, confirm the fill starts when expected and stops at the approved upper level. Then test the high and low alarm points separately.

For pump down controls, verify each pump start and stop point and any high level alarm.

Do not jump directly to the alarms without proving normal operation first.

Verify Water Level Controller Outputs With Press-to-Test

The WLC-5000 water level controller has a push-button relay test, and other Waterline Controls models have a similar function.

The installation instructions for the FPT-40 fire protection water level controller, an alarm-only model, describe a test of about two minutes that automatically sequences through the controller functions, cannot be interrupted once started and is intended to exercise the dry contacts and power relays with the devices connected. The WLC-6100T controller runs a similar test through its outputs.

Before pressing the test button, confirm which outputs and remote alarms the selected model will exercise. Coordinate with building staff and secure any connected loads that must stay off during the test.

The test is useful, but it does not replace checking actual sensor elevations and real water response.

Verify Every BMS and SCADA Point

Have the controls contractor watch the remote system while each condition is created.

For each specified point, verify its name, signal source, normal and active states, and return to normal. Where the design calls for proof that a pump is running, verify feedback from the starter or drive. The BMS points a water level controller should report make a useful starting list.

If a point is reversed, correct it during commissioning and retest the normal and alarm states.

Check alarm delays and notification routing as part of the same process.

Simulate Power Loss

Under the approved test procedure, coordinate the interruption with operations and any affected monitoring station before removing controller power.

Verify that each affected output and connected device reaches its specified state. Where remote power loss or fault reporting is specified, verify that the receiving system indicates it and clears it after power is restored. What happens to level control during power loss explains the states to expect.

Restore power and confirm the controller returns to normal operation without creating an unintended command.

Critical applications may require additional emergency testing according to the project requirements.

Record the Final Settings

Leave useful information for the people who will maintain the system. For each test, record:

  • the sensor elevation and any custom sensor dimension
  • the expected response from the sequence of operation
  • the observed local and remote responses
  • pass or fail, and any corrective action
  • relay functions, BMS point names and valve or pump assignments

Future troubleshooting becomes much easier when the technician knows what normal operation looked like on commissioning day.

Commissioning Support for Water Level Controls

Waterline Controls manufactures frequency-based electronic water level controllers for cooling towers, tanks, sumps, wastewater systems and fire protection applications, with model-specific options for sensor length, local indication, relay outputs, remote signaling and output testing. Call 480-905-1892 to review the control sequence, installation requirements and commissioning functions for the Waterline Controls system specified on your project.